Specification of Cutler Hammer S811+V65N3S/S811+V65N3S cutler hammer/S811+V65N3S cutler EATON
S811+V65N3S
Soft starter, 650 A, 200 - 600 V AC, Us= 24 V DC, with control unit, Frame size V
Alternate Catalog No.
S811PLUSV65N3S
EL-Nummer (Norway)
4137486
Soft starter, Description: With internal bypass contacts, Function: Soft starter for three-phase loads, with control unit, Mains supply voltage (50/60 Hz): ULN= 200 - 600 V AC, Supply voltage: Us= 24 V DC, Control voltage: UC= 24 V DC, Assigned motor rating (Standard connection, In-Line) at 400 V, 50 Hz: P= 315 kW, at 460 V, 60 Hz: P= 500 HP, Rated operational current AC-53: Ie= 650 A, Rated operational current AC-53, In-Delta: Ie= 1125 A, Startup class: CLASS 10 (star-delta replacement), CLASS 20 (heavy starting duty 3 x Ie for 45 s), CLASS 30 (6 x Ie for 30 s), Rated operational voltage: Ue= 200 V, 230 V, 400 V, 480 V, 600 V, Connection to SmartWire-DT: no, Frame size: V, Ordering information: Terminal blocks for the terminals are required for frame sizes T, U, and V -> Accessories, Standards: IEC/EN 60947-4-2, UL 508, CSA22.2-14-1995, GB14048